Pressure Transmitter Module Set For Silicon Sensor
- Microcyber
- Liaoning, China
- In Stock
- 500 Sets/Month
HART piezoresistance silicon pressure module set MS0110, using the fieldbus technology, is a new generation of smart temperature module and it is an indispensable field device for process control. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.thermal resistance and thermocouples sensors.
Hart Communicator Modem: In the instruments industry, the traditional 4 – 20 mA analog transmitters are upgrading to the fieldbus with digital communication.
HART temperature board MS0210, using the fieldbus technology, is a new generation of smart temperature module and it is an indispensable field device for process control. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
HART temperature board uses digital technology and it shall match multiple thermal resistance and thermocouples sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
Dimension:
The hardware interface of HART temperature board set :
There are 3 main interfaces for HART temperature board set:
Alarm setting (AL) and configuration protection setting (WP) hardware DIP switch;
J1, HART bus power interface (P+ and P-);
J5, temperature sensor connection interface.
Sensor Wiring
HART temperature set sensor wiring support 2-wire, 3-wire and 4-wire.
TC represents thermocouple type sensor, mV represent voltage signal, Ω represents resistive and RTD represents thermal resistive type sensor.
System Connection
Basic Parameter
Content | Index |
Bus Connection | (4~20)mA + HART |
Bus Power | (10.5~42)VDC (10.5~30)VDC (Intrinsically Safety) |
Load Resistive | (0~1500)Ω (Normal) (230~550)Ω (With HART) |
Input Signal | Pt100, Pt1000, CU50, CU100, (0~500)Ω, (0~4000)Ω resistance; B, E, J, N, K, R, S, T thermal couples; (-100~100) mV voltage signals. |
Channel | Single channel |
RTD Wiring | 2/3/4 wire |
Display | COG128x64 |
Working Temperature | (-20~70)℃ |
Storage Temperature | (-40~85)℃ |
Start Time | ≤5s |
Refresh Time | 0.5s |
Humility Range | (5~95)% RH |
Isolation Voltage | 500 VAC |
EMC | GB/T 18268.1-2010 GB/T 18268.23-2010 |
RTD Parameter
RTD Parameter at Normal Temperature (25℃)
Signal Type | Suggested Range (℃) | Accuracy |
Resistance Signal | (0~500) Ω, (0~4000) Ω |
±0.09Ω /±0.7 Ω |
PT100 | (-200~850) ℃ | ±0.3 ℃ |
PT1000 | (-200~850) ℃ | ±0.3 ℃ |
CU50 | (-50~150) ℃ | ±0.5 ℃ |
CU100 | (-50~150) ℃ | ±0.4 ℃ |
RTD Other Parameter
Wiring | 2/3/4 |
Common Mode Rejection | ≥70 dB (50 Hz and 60 Hz) |
Series Mode Rejection | ≥70 dB (50 Hz and 60 Hz) |
Temperature Effect | <50 ppm/℃ |
Thermocouple Parameter
Thermocouple Parameter at Normal Temperature (25℃)
Signal Type | Suggested Range (℃) | Accuracy |
mV | (-100~100) mV | 0.05% |
B | (500~1810) ℃ | ±1.0℃ |
E | (-200~1000) ℃ | ±0.4℃ |
J | (-190~1200) ℃ | ±0.4℃ |
K | (-200~1372) ℃ | ±0.4℃ |
N | (-190~1300) ℃ | ±0.8℃ |
R | (0~1768) ℃ | ±1.0℃ |
S | (0~1768) ℃ | ±1.0℃ |
T | (-200~400) ℃ | ±0.4℃ |
Thermocouple Other Parameter
Compensation Accuracy | (-2~5) ℃ |
Sensor Type | B, E, J, N, K, R, S, T; (-100~100)mV Voltage |
Common Mode Rejection | ≥70 dB (50 Hz and 60 Hz) |
Series Mode Rejection | ≥70 dB (50 Hz and 60 Hz) |
Temperature Effect | <50 ppm/℃ |