Fieldbus Devices(Modbus to HART Gateway )
- Microcyber
- China
- In Stock
- 500 Sets/Month
G0310 Modbus to HART Gateway, designed by Microcyber Corporation is a gateway device for Modbus-RTU protocol and HART protocol. As Modbus master, G0310 Modbus to HART Gateway communicates with devices that have Modbus-RTU communication function via RS485 interface. It can convert device data to HART device variables output, and it also supports 4~20mAcurrent output.
G0310 Modbus to HART Converter designed by Microcyber Corporation is a gateway device for Modbus-RTU protocol and HART protocol. As Modbus master, G0310 Modbus to HART Gateway communicates with devices that have Modbus-RTU communication function via RS485 interface. It can convert device data to HART device variables output, and it also supports 4~20mAcurrent output.
Modbus to HART Gateway Features
Be tallied with HART7.0
HART slave and Modbus master mode
4~20mA analog signal overlay HART digital signal
Support 1 Modbus slave device
Support 6 device variables and 4 dynamic variables
Configure gateway by HART interface
Write protect user data
Support high/low alarm current
RS485 Modbus interface
LED power and communication indicating
Standard DIN rail installation
Modbus-RTU protocol to HART protocol
Support 6 device variables and 4 dynamic variables
Support Modbus communication parameters dynamic configuration
Support HART multipoint mode
Support 375/475 communicator
Modbus to HART Gateway Parameters
Modbus to HART Gateway Basic parameter
Measurement Object: Modbus RTU slave device
Power: 12~42VDC
Bus Protocol: 2-wire,4~20mA+HART
Load resistance: 0~1500Ω(4~20mA)
230~1100Ω(HART communication)
Isolation Voltage: Modbus and HART Bus Interface,500VAC
Temperature Range: -40℃~85℃
Humility Range: 5~95%RH
Start Time: ≤5s
Refresh Time: 0.2s
Damping adjustment: Time constant 0~32s
Modbus to HART Gateway Dimension
Dimension(Unit: mm)
Modbus to HART Gateway Structure
Modbus to HART Gateway Installation
Wiring
Dimension of G0310 MODBUS to HART gateway is 99×22.5×114.5mm, supporting standard DIN guide rail installation.
The power supply of G0310 MODBUS to HART gateway is HART bus, and 485 communication need external 24V power supply. The recommended is TP cable, and it shall improve device’s anti-electromagnetic interference ability.
Modbus to HART Gateway Jumper configuration
G0310 MODBUS to HART Gateway has 2 jumpers, as shown on picture.The left one is failure warning current setting and the right one is configuration protection setting jumper.
G0310 Modbus to Hart Gateway Jumper
Failure Warning Jumper Setting
G0310 MODBUS to HART Gateway has self-diagnostic function. Once failure is found, intelligent instrument will output warning current automatically. Warning current mode is decided by failure warning current jumper on the left of the board. When there’s no insertion or insertion of two points underside, it’s high-level warning (warning current≥21.75mA);When it’s the insertion of two points upside, it’s low-level warning (warning current≤3.7mA).
Configuration Protection Jumper Setting
G0310 MODBUS to HART Gateway provides jumper setting of device configuration protection or not, that is the configuration protection setting jumper described above, as shown on figure 3. When it’s the insertion of two points upside, it’s configuration protection. At this moment no change of device configuration is allowed. It is allowed when there’s no insertion or insertion of two points underside.
Saturation fixed output (manufacturer setting, no configuration)
When HART intelligent instrument is running, it will compare PV and range upper and lower limiting value constantly. When PV exceeds the limit, instrument will output fixed current. When PV is higher than upper limit, it output 20.8mA;When PV is lower than upper limit, it output 3.8mA.
Working Principle
G0310 MODBUS to HART gateway connection diagram is shown asfollowing:
G0310 MODBUS to HART gateway connection diagram
G0310 MODBUS to HART Gateway supports 4 dynamic variables, 6 device variables. Via MODBUS register, the data selected by MODBUS device is configured to device variables of G0310 MODBUS to HART Gateway, and then, it enters the mapping from device variable to dynamic variable, as the device output, supporting 4~20mA analog signal output. G0310 MODBUS to HART Gateway functional block diagram is shown as on picture:
How To Choose G0310 Modbus to HART Gateway?
Appendix Model Selection
FAQ
Q: Can I get a free electronic manual?
A: Yes, if you want it, please contact us.
Q: How is the gateway configured?
A: G0310 MODBUS to HART support standard HART device connection: point to point and multipoint connection. User can use Microcyber HartMPT configuration.
Q: Can you provided OEM service?
A: Yes, we can, such as communication board, we can also provided fieldbus development toolkit.
Related Products--Modbus to HART Gateway