NCS-TT105 smart temperature transmitter
NCS-TT105 smart temperature transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT105 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT105 uses digital technology, so it can connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
NCS-TT105 supports HART, FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
Installation
For installation of NCS-TT105 temperature transmitter, three types of bracket (pipe mounting flat bracket, plate mounting angle bracket and pipe mounting angle bracket) are provided. Accordingly there are three installation methods as the following.
The installation of pipe mounting flat bracket: the typical installation . Fix NCS-TT105 temperature transmitter in flat bracket using four bolts provided, and then fix the flat bracket on the vertical pipe in Φ50mm around with the U-shape bolt provided.
The installation of plate mounting angle bracket: the typical installation . Fix NCS-TT105 temperature transmitter in angle bracket using four bolts provided, and then fix the angle bracket on the plate with the M10 bolt not provided.
The installation of pipe mounting angle bracket: the typical installation , NCS-TT105 temperature transmitter in angle bracket using four bolts provided, and then fix the angle bracket on the horizontal pipe in Φ50mm around with the U-shape bolt provided.
Basic Parameters
Resistance: PT100, PT1000, CU50, CU100, 0~500Ω, 0~4000Ω Thermocouple: B, E, J, N, K, R, S, T Voltage signal: -100mV~100mV | |
Channels | 2 Channels |
RTD connection | 2, 3 wire |
Power Supply of Fieldbus | FF/PA:9~32 VDC/Current : ≤ 14mA HART: 12~42VDC |
Insulation | Between housing and terminal board: 500 Vrms (707 VDC) |
Display | 6-digit numeric and 5-digit alphabet LCD Display |
Operation Temperature | -40 ~ 85℃ (Without display) -30 ~ 70℃ (With display) |
Humidity Range | 0% ~ 100% RH |
Start Time | ≤ 5s |
Update Time | 0.2s |
Protection grade | IP 65 |
EMC | Designed to comply IEC 61000 (GB/T 18268-2000) |