Brief Introduction

The NCS-PT105 Series is a complete line of smart transmitters for differential, absolute, gauge, high static differential pressure and micro differential pressure. The NCS-PT105 Series is a robust and highly reliable solution for your process. The large acceptance of the  NCS-PT105 line is due to the use of a capacitive cell as pressure sensor, which keeps the digital signal from the pressure reading up to the transmitter output, increasing the device accuracy and stability. Three options of communications protocols for configuration, monitoring and diagnostic are available: HART®, FOUNDATION™ fieldbus and PROFIBUS PA.  

Model

According to the type of measurable pressure:
ModelPressure type
NCS-PT105II SGGauge Pressure Transmitter
NCS-PT105II SAAbsolute Pressure Transmitter
NCS-PT105II SDDifferential Pressure Transmitter
NCS-PT105II SHDifferential Pressure Transmitter For High Static Pressure
According to the protocol:
ModelPressure type
NCS-PT105II FFF H1
NCS-PT105II PPROFIBUS PA

Size 

pressure transmitterpressure transmitter application

Basic Parameters


Measure Objectliquid,gas,stream
Power9~32V DC(FF,PA)
9~32V dc (FF, PA Explosion-proof instrument)
11.9~42 V DC (HART)
11.9~30 V DC (HART Explosion-proof instrument)
OutputAnalog: 2 wire 4~20mA
Digital: HART, FF and PA signal
Load resistant0~1500ohm (common)
250~550ohm (with HART)
InsulationInput and output insulating voltage: 500Vrms (707VDC)
DisplayOptional 6 bits digital number or 5 bits characters LCD display
Temperature scaleWork temperature: -40 ~ 85°C (No display)
-30 ~ 70°C (display)
-30 ~ 60°C (Explosion-proof)
Store temperature:   -40 ~ 100°C (No display)
-40 ~ 85°C (display)
Allowed media temperature measured-40 °C~ 110 °C (Type name include ‘IC’)
-40 °C~ 149 °C (silicone oil)
-40 °C~ 204 °C (sylthlem800)
-18 °C~ 204 °C (inert liquid)
-40 °C~ 104 °C (others)
Humidity scale5%~100%RH
Start time≤ 5 seconds
Refresh time0.2 seconds
Dump adjustingTime constant 0~15 seconds
Change of cavity< 0.16 cm3
Static pressure limitSRRange 2: 1000psi (6.89MPa)
SDRange 3~8: 2000psi (13.8MPa)
SGRange 3~8: 2000psi (13.8MPa)
Range 9: 4500psi (31.0MPa)
Range 0: 7500psi (51.7MPa)
SARange 4: 58psi (400kPa)
Range 5: 218psi (1500kPa)
Range 6: 435psi (3000kPa)
SHRange 4~7: 4500psi (31.0MPa)