Industrial Differential Pressure Transmitter with FF H1 Protocol Universal Input Intelligent Pressure Gauge
Industrial Differential Pressure Transmitter with FF H1 Protocol Universal Input Intelligent Pressure Gauge
Brief Introduction
The NCS-PT105 Series is a complete line of smart transmitters for differential, absolute, gauge, high static differential pressure and micro differential pressure. The NCS-PT105 Series is a robust and highly reliable solution for your process. The large acceptance of the NCS-PT105 line is due to the use of a capacitive cell as pressure sensor, which keeps the digital signal from the pressure reading up to the transmitter output, increasing the device accuracy and stability. Three options of communications protocols for configuration, monitoring and diagnostic are available: HART®, FOUNDATION™ fieldbus and PROFIBUS PA.
Model
According to the type of measurable pressure: | |
Model | Pressure type |
NCS-PT105II SG | Gauge Pressure Transmitter |
NCS-PT105II SA | Absolute Pressure Transmitter |
NCS-PT105II SD | Differential Pressure Transmitter |
NCS-PT105II SH | Differential Pressure Transmitter For High Static Pressure |
According to the protocol: | |
Model | Pressure type |
NCS-PT105II F | FF H1 |
NCS-PT105II P | PROFIBUS PA |
Size
Basic Parameters
Measure Object | liquid,gas,stream | |
Power | 9~32V DC(FF,PA) | |
9~32V dc (FF, PA Explosion-proof instrument) | ||
11.9~42 V DC (HART) | ||
11.9~30 V DC (HART Explosion-proof instrument) | ||
Output | Analog: 2 wire 4~20mA | |
Digital: HART, FF and PA signal | ||
Load resistant | 0~1500ohm (common) | |
250~550ohm (with HART) | ||
Insulation | Input and output insulating voltage: 500Vrms (707VDC) | |
Display | Optional 6 bits digital number or 5 bits characters LCD display | |
Temperature scale | Work temperature: -40 ~ 85°C (No display) | |
-30 ~ 70°C (display) | ||
-30 ~ 60°C (Explosion-proof) | ||
Store temperature: -40 ~ 100°C (No display) | ||
-40 ~ 85°C (display) | ||
Allowed media temperature measured | -40 °C~ 110 °C (Type name include ‘IC’) | |
-40 °C~ 149 °C (silicone oil) | ||
-40 °C~ 204 °C (sylthlem800) | ||
-18 °C~ 204 °C (inert liquid) | ||
-40 °C~ 104 °C (others) | ||
Humidity scale | 5%~100%RH | |
Start time | ≤ 5 seconds | |
Refresh time | 0.2 seconds | |
Dump adjusting | Time constant 0~15 seconds | |
Change of cavity | < 0.16 cm3 | |
Static pressure limit | SR | Range 2: 1000psi (6.89MPa) |
SD | Range 3~8: 2000psi (13.8MPa) | |
SG | Range 3~8: 2000psi (13.8MPa) | |
Range 9: 4500psi (31.0MPa) | ||
Range 0: 7500psi (51.7MPa) | ||
SA | Range 4: 58psi (400kPa) | |
Range 5: 218psi (1500kPa) | ||
Range 6: 435psi (3000kPa) | ||
SH | Range 4~7: 4500psi (31.0MPa) |