G0313 MODBUS RTU to FF DIN Rail Mounting Gateway

20-02-2023

G0313 Modbus to FF Gateway is a gateway device of Modbus protocol and FF protocol developed by Microcyber. As Modbus master station, G0313 Modbus to FF Gateway communicates with Modbus-RTU device via RS485 interface, and it can convert the data of Modbus-RTU device to FF device variable output. G0313 Modbus to FF Gateway is shown in Figure 1:

G0313 Modbus to FF Gateway

Outer Size Diagram


Modbus to Fieldbus Converter FF Gateway


Figure 2 Outer Size of Gateway Device (Unit: mm)


 Configuration of DIP Switch

 

There is a 3-bit DIP switch for G0313 Modbus to FF Gateway, shown as Figure 5.

SIM: Simulation switch, used for “simulation function”.

WP: Write protection, all the write operation for FF smart pressure transmitter shall be refused, which avoid data modification at random.

RST: Reset, reset device date to factory original. Power off the device at first, and m ade the switch at ON, and then power on the device, the device shall be reset to factory original.


industrial iot gateway


Introduction for Function


Default configuration of Modbus to FF Gateway has 1 RES function block, 4 for each AI, AO, DI, DO, PID function block and Modbus transducer block (Modbus_TB ) complying to FF specifications. AI, AO, DI, DO respectively supports 8 channels (CHANNEL ), each channel is corresponding to analog/discrete input and output parameters of Modbus transducer block.


Function Block name

Description

 

 

Resource (RES)

Resource block is used to describe the device identity in the field, such as device name,

manufacture, serial number. There is no input or output parameter in the resource block. Generally, there is only one resource block for each device.

 

Modbus_TB (MTB)

Configure Modbus communication parameters via transducer block, such as baud rate, stop bit,

communication overtime, etc., Modbus communication configuration parameter.

 

Analog Input (AI)

Analog input function block is used to achieve transducer block input data and transfer to other

function blocks, has the function of range conversion, square root, cut mantissa, etc.

 

Analog Output (AO)

Analog output function block is used to transfer output data to transducer block, then to operate

physical device.

 

Discrete Input (DI)

Discrete input function block, achieve transducer block input data and transfer to other functions

blocks.

 

Discrete Output (DO)

Discrete output function block is used to transfer discrete output data to transducer block, then to

operate physical device.

Proportional Integral

Derivative(PID)

PID function block has the function of PID control and setting point adjustment, process

value(PV) filtering and alarm, output tracking, etc.


4.1 Communication Parameter for Modbus Transducer Block

The user is able to configure the Modbus communication parameter, such as baud rate, stop bit, communication timeout, etc. The Modbus communication configuration parameters are shown as following:


Parameter Name

 Data Type

 Function Description

 MEDIA

 USIGN8

Physical transmission medium, 0:RS232,1:RS485

 BAUD_RATE

 USIGN8

Baud rate,0:9600(default),1:19200,2:15625,3:31250,4:62500,5:125000

 STOP_BIT

 USIGN8

Stop bit,0:one stop bit,1:two stop bits

 PARITY

 USIGN8

Calibration bit,0:no calibration bit,1:even calibration,2:odd calibration

 CRC_ORDER

 USIGN8

CRC calibration byte order,0:high byte first,1:low byte first

 TIME_OUT

 USIGN16

After sending MODBUS request, the maximum time waiting for slave station

response. The unit is ms, default 300ms.

 NUMBER_OF_RETRY

 USIGN8

When the waiting response is timeout, the number for resending the request. The

range is 0-255.

 SLAVE_ADDRESS

 USIGN8

 Address for MODBUS slave station. The range is 0-255.




Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy