HART Temperature Transmitter Configuration Information Setting

21-03-2020

NCS-TT106  Temperature Transmitter

HART Temperature Transmitter Configuration

Function Configuration

Configuration Information Setting

 

Through configuration information dialog, the configuration information of smart transmitter can be read or modified, including displayed device output variable (primary variable, cold end temperature value, current value and percentage), primary variable info setting (damp value, unit, upper limit and lower limit) and range calibration, etc.,shown as picture. 

HART Temperature Transmitter

Configuration Information


Damp: range 0~32s

Unit: PV unit modification affects variables related to unit, such as the upper or lower limit for the range or for the sensor. When you modify the unit, you can’t modify upper or lower limit for the primary variable range, instead, you should modify them separately.

The unit can be set as:゜C,゜F,゜R, K, mV, Ohm.

Upper limit of the range: Corresponding to PV value of 20mA output current.

Lower limit of the range: Corresponding to PV value of 4mA output current.

You should press “Apply” to download it into device after the modification.

Set “upper limit of range” with present value: Set the PV as the upper limit of primary variable range, and keep the lower limit of range the same as previously.

Set “lower limit of range” with present value: Set the PV as the lower limit of primary variable range, it may probably modify upper limit at the same time.

Set “primary variable zero point” with present value: Set the PV as the primary variable zero point when the temperature is 0゜C.