NCS-TT106 smart temperature module, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT106 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
1. Support the latest versions of FF H1, PROFIBUS PA and HART protocols
2. Support 6 types of thermal resistance and 8 types of thermocouple
3. Support 2-channel sensor input
4. Thermal resistance supports 2-wire, 3-wire and 4-wire
5. The cold end compensation accuracy of thermocouple is ±0.5 ℃
6. High precision (better than grade 0.1), low temperature drift (better than ±50ppm/℃ )
7. Comply with FCG interoperability specification (ITK 6 and HART 7), PNO interoperability test certification (PA profile 3.02)
8. Explosion-proof (intrinsically safe, flameproof) certification

Description


NCS-TT106 Head Mounted Temperature Transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT106 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.

 

NCS Series of Intelligent Transmitters are digital, intelligent, network-based, merged with advanced, reliable and stable sensor technology, to be designed as a new generation of Fieldbus Intelligent Transmitter.

 

NCS Series of Intelligent Transmitter have been designed with high precision and high reliability, high stability. The pressure, temperature, currents and other physical quantities are displayed on LCD module. Zero drift, range settings and many other functions, are realized by the magnetism bar operation. The interoperability between different systems and equipments are realized by the Equipment Description Document, which is compatible to a variety of device management software, and adapting to harsh electromagnetic environment. NCS Series of Intelligent Transmitter have been used in inflammable and explosive places according to Intrinsically Safety Design.


NCS-TT106 uses digital technology, so it can connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.



Features


NCS-TT106 Head Mounted Temperature Transmitter

Support multiple thermal resistances and thermocouples;

Thermal resistance supports 2/3/4-wire connection mode;

Thermocouple can use cold end compensation function;


Basic Parameter


Basic Parameters

Bus Power Supply

9~32VDC Current consumption (static):≤14mA(FF/PA)
11V~35 VDC(HART)

Input Signal

Pt100, Pt1000, Cu50, Cu100 Ω, 0, 0 to 500 ~ 4000 Ω Resistance
B, E, J, N, K, R, S, T eight degrees of Thermocouple
-100mV ~ 100mV Voltage Signal

The Channel Number

Single Channel

Fieldbus Protocol

FF/PA/HART

Insulation

Between the Terminal and the Housing:500Vrms(707VDC)

Operating Temperature

-40℃~85℃

Humidity Range

0%~95%RH

Starting Time

≤5secs.

Turnover Time

0.5secs.

Electromagnetic Compatibility

In Line with the GB/T 18268-2010

Explosion-Proof Sign

Ex ia IIC T4 Ga(HART)


NCS-TT106 Head Mounted Temperature Transmitter


Input Signal

Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω

B,E,J,N,K,R,S,T eight kinds of Thermocouple

-100mV~100mV voltage signal

Channel

Single

RTD Wiring

2-wire, 3-wire, 4-wire

Bus Power

HART: 11~35 VDC  

Bus Signal

HART,current mode

Electric isolation

1000VAC

Working Temperature

-40℃~85

Humidity Range

5%~95%RH

Start Time

≤5s

Refresh Time

0.5s

EMC

GB/T 18268.1-2010

Protection

Terminal IP00, housing IP40

Voltage effect

±0.005%/V

Alarm signal

Alarm output can be set as   3.5…23 mA

Upper/lower limit current    20.8mA / 3.8mA

Current accuracy

0.03%


NCS-TT106F  Foundation Fieldbus


Bus interface

FF

Bus power

9~32VDC

Input Signal

Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω Resistance;

B E J K N R S T Thermocouple、-100mV~100mV、Custom defined TC、Custom defined RTD

Channel

Single

RTD Wiring

2-wire, 3-wire, 4-wire

Refresh Time

0.5s

Working Temperature

-40~85

Storage temperature

-40~85

Humidity Range

5~95%RH

Electric isolation

1000VAC

Voltage effect

±0.005%/V

Protection

Terminal IP00, housing IP40

EMC

GB/T 18268.1-2010

GB/T 18268.25-2010


RTD Parameter

RTD Parameter at Normal Temperature(25℃)


Signal type

Suggested range

Accuracy(25

Temperature drift(per

Resistance Signal

0~500Ω

±0.04Ω

±0.001Ω

0~ 4000Ω

±0.35Ω

±0.015Ω

PT100

-200~850℃

±0.15℃

±0.003℃

PT1000

-200~850℃

±0.15℃

±0.005℃

CU50

-50~150℃

±0.15℃

±0.005℃

CU100

-50~150℃

±0.10℃

±0.003℃


Thermocouple

Thermocouple Parameter at Normal Temperature(25℃)


Signal type

Suggested range

Accuracy(25

Temperature drift(per

mV

-100mV~+100mV

±0.025mV

±0.001 mV

B

500℃~1810℃

±0.77℃

±0.050℃

E

-200℃~1000℃

±0.20℃

±0.025℃

J

-190℃~1200℃

±0.35℃

±0.01℃

K

-200℃~1372℃

±0.40℃

±0.025℃

N

-190℃~1300℃

±0.50℃

±0.015℃

R

0℃~1768℃

±0.75℃

±0.023℃

S

0℃~1768℃

±0.70℃

±0.023℃

T

-200℃~400℃

±0.35℃

±0.015℃



Dimension


PROFIBUS PA Genuine authorization thermometer head mounted temperature transmitter

Temperature Module Dimension (Unit: mm)


Installation


Via positioning hole, use two screws to install the temperature module to temperature housing or rail.


head mounted temperature transmitter

                            temperature transmitter


Wiring

PROFIBUS PA Genuine authorization thermometer head mounted temperature transmitter

Fieldbus temperature module’s power and bus signal share a pair of cable, and it is called bus cable. It is suggested the user use fieldbus special cable recommended by IEC61158-2.

The signal cable and bus cable cannot share wires or wire slot with other device power wire, and they shall be away from device with high power.

The shielded wires of bus ends shall be connected to the ground.


Application

head mounted temperature transmitter

Certificates

  temperature transmitter


FAQ

Q: What’s Temperature Transmitter 2-wire zero point calibration configuration?

A: For 2-wire measurement, 2-wire zero point calibration can be realized by modifying transducer block TWO_WIRES_COMPENSATION parameter.

 

Q: Can I get the electronic manual?

A: Yes, please contact us.

 

Q: What type of cable should I use for wiring?

A: Fieldbus temperature module’s power and bus signal share a pair of cable, and it is called bus cable. It is suggested the user use fieldbus special cable recommended by IEC61158-2.

 

Q: Can you provided OEM service?

A: Yes, we can, such as communication board, we can also provided fieldbus development toolkit.


Hot Products

PROFIBUS PA Genuine authorization thermometer head mounted temperature transmitterhead mounted temperature transmittertemperature transmitter



Quality Control
Quality Control
Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right